Petroprema supplies premium heating cables providing both freeze protection and process temperature maintenance for metallic piping as well as non-metallic piping, tanks and equipment. The heat output of the cable is designed to change depending on conditions throughout the circuit. As heat loss from the equipment increases, heat output from the cable increases. As the heat output decreases as the ambient temperature increases, the cable output also decreases. 

Selfregulating heating cable tracing frost protection TRACECO

TRACECO-T® Heat tracing cable for frost protection

The ideal cable type, the best-seller of self-regulating cables, a standard recognized for its thermal qualities and longevity. Ideal for protecting pipes, gutters and tanks against freezing. The TRACECO-T is a self-regulating electric heating cable for frost protection of EG chilled water, EF cold water, EU waste water, EP rainwater pipes. No risk of pipes bursting due to frost thanks to “self-regulating” technology. No overheating possible therefore completely secure. The colder it is and the hotter it is, the hotter it is, the less energy it uses. It can be cut to the desired length directly on site. Can be used with the DOMOCLICK® quick connection system.

Construction of cable TRACECO-T

1- Conductors formed from 2 strands of nickel-plated copper composed of 19 wires of 0.287mm in diameter and section 1.23mm²

2- Semiconductor matrix crosslinked by irradiation​

3- Crosslinked gray polyolefin insulation

4- Shielding with aluminum tape + drain

5- Black Thermoplastic Sheath

 

Power curve of the self-regulating heating cable TRACECO

Nominal values of the electric tracer​

Rated supply voltage 230V​

Power tolerances -0/+5 W​

Maximum exposure temperature under voltage 65°C

Maximum exposure temperature without power 80°C

Temperature class T5/T6

Minimum bending radius 27 mm​

Minimal installation temperature - 35°C

Theoretic weight 90-105 kg/km

Theoretic weight (braided) 105-126 kg/km

Maximum resistance of the ground conductor at 20 °C 15.29 Ω/km 

Maximum circuit length :

TRACECO-10…………. 215 m

TRACECO-20…………. 170 m

TRACECO-30…………. 140 m

TRACECO-40…………. 120 m

Qualification Products

Certificates CSTB, EAC, CE, IP67, UV-résistant, RoHS, REACH




 

Selfregulating tracing heating cable TRACECO elevated higher temperature

TRACECO Class W - Self regulating heating cable for elevated temperatures

For maintaining the temperature of pipes or tanks of hot water, swill, or other greases.... This class of tracer also makes it possible to fight against Legionnaires' disease in pipes. They are designed to prevent any risk of pipes bursting due to freezing. The “self-regulating” technology allows for safe use: Adapts its electricity consumption according to needs and prevents any overheating..

When it is cold, the polymer contracts and facilitates the passage of current, which allows an increase in the temperature of the cable. The hotter it is, the more the polymer expands and prevents the flow of current: the cable heats up less.

Finally, so-called “parallel” technology allows the heating cables to be cut to the desired length directly on site, in order to precisely adapt the length of the heating cable to your needs.

The BOX type reel storage system allows simple, quick and practical handling. This product is available in stock and can be used with the DOMOCLICK® quick connection system

By using our TRACECO-W type tracers, you ensure the best electrical tracing system.

Construction of cable TRACECO-W

  1. Conductors made up of 2 nickel-plated copper strands composed of 19 wires of 0.287mm in diameter and 1.23mm² section
  2. Semiconductor matrix crosslinked by irradiation
  3. Cross-linked gray polyolefin insulation
  4. Shielding with tinned copper braid or aluminum tape + drain
  5. Grey Thermoplastic Sheath

Nominal values of the electric tracer​

  • Rated supply voltage 230V​
  • Power tolerances -0/+5 W​
  • Maximum exposure temperature under voltage 80°C
  • Maximum exposure temperature without power 100°C
  • Minimum bending radius 27 mm​
  • Minimal installation temperature - 20°C
  • Theoretic weight 90-105 kg/km
  • Theoretic weight (braided) 105-126 kg/km
  • Maximum circuit length :
    • TRACECO-W-55…………. 130 m
    • TRACECO-W-65…………. 110 m

Certificates CSTB, GOST-R, EAC, CE, IP67

 

Selfregulating heating cable tracing high temperature ESR

ESR Class H - Self regulating heating cable for high temperatures 

High Temperature Maintenance of Pipes, Tanks, in corrosive atmosphere...

High temperature self-regulating heating tape for Industry. Withstands 200°C off thanks to ultra temperature resistant materials and up to 120°C under power.

Can be used in healthy areas as well as in corrosive or explosive areas. These heating ribbons can be used on pipes as well as on tanks.

By using our ESR-H-BOT type tracers you ensure the best electrical tracing system. They are designed to maintain a high temperature for your pipes, valves and tanks. Its “self-regulating” technology allows for simple, safe use. The self-regulated power of the cables varies according to the surrounding temperature and prevents overheating.

Finally, so-called “parallel” technology allows the heating cables to be cut to the desired length directly on site, in order to precisely adapt the length of the heating cable to your needs. Its BOX type reel storage system allows simple, quick and practical handling. This product is available in stock.

Construction of cable ESR-H-BOT

1- Conductors formed from 2 strands of nickel-plated copper composed of 19 wires of 0.287 mm in diameter and section 1.23 mm²

2- Semiconductor matrix crosslinked by irradiation​

3- Insulation

4- Shielding with tinned copper braid or aluminum tape + drain

5- Red Fluoropolymer sheath

Power curve of the heating cable ESR-H-BOT

Temperature class under voltage: T3 (T2 pour le 60W/m)

Minimum bending radius 30 mm

Minimal installation temperature - 40 °C

Theoretic weight (braided) 119 kg/km

Maximum circuit length :

  • ESR-H-BOT-60…………. 205 m
  • ESR-H-BOT-60…………. 190 m
  • ESR-H-BOT-60…………. 115 m
  • ESR-H-BOT-60…………. 85 m
  • ESR-H-BOT-60…………. 65 m

Qualification Products

Certificates ATEX, GOST-R, EAC, CE



SELF REGULATING HEAT TRACING CABLE​

Properties of the heating cable

• Self regulating

• 4 different power outputs

• Cut-to-length

• Resistant to UV

Technical specifications​

Maximum exposure temperature (power off): 85°C

Maximum operating temperature : 65°C

Nominal tension : 230V

Minimal bending radius : 25 mm

Minimal installation temperature : -50°C

Buswires: nickel-plated copper​

Applications

ThermTrace Lite is an industrial grade, self-regulating heating tape designed for a wide range of applications. It can be used for freeze protection or low temperature maintenance of pipes and tanks in hazardous areas, as well as for heating roofs and gutters in the construction industry.

Properties of the heating cable

Name

 W/M

T° max. 

Dimensions

12 TTL-2-BO

12

85

10,5x5,6

23 TTL-2-BO

23

85

10,5x5,6

TTL-2-BO : Cable with protective braid and thermoplastic oversheath

Self regulating heating cable tracing HTS Thermtrace


SELF REGULATING HEAT TRACING CABLE​

Properties of the heating cable

• Self regulating

• 2 power outputs

• Cut-to-length

• Resistant to humidity

• Tracing of grease pipes

Technical specifications​

Maximum exposure temperature (power off): 100°C

Maximum operating temperature: 80°C

Nominal tension : 230V

Minimal bending radius : 20 mm

Minimum installation temperature : -20°C

Buswires: nickel-plated copper​

Applications


ThermTrace WaterHeat is a construction-grade, self-regulating heating cable specifically designed for hot water systems. It serves to protect against frost, maintain temperature and prevent the formation of legionella. 33 TTWH is frequently used to heat oil and grease lines, for example in the food industry.


Name

 W/M

T° max

Dimensions

25 TTWH-2-BO 

9 W/m at 55°C 

100

13,0 x 5,0

33 TTWH-2-BO 

W/m at 55°C

100

13,0 x 5,0

Selfregulating heating cable high temperature tracing HTS