ZELFREGELEND VERWARMINGSLINT TRACECO-10 met afscherming. aarding en overmanteling.
10 jaar garantie op onze verwarmingskabels ! Properties of heating tape
• Self-regulating 12W/m @5°C • Cut-to-length • UV-resistant
Technical data :Cable with protective aluminium foil AND thermoplastic overjacket
Max. exposure t° (unpowered): 80°C Max. operating temperature: 65°C
Nominal voltage: 230V Min. bending radius: 25mm Min. installation t°: -25°C
Buswires: nickel plated copper Dimension : 12.5x5mm
Max. recommended length of heating circuit at 230 VAC using Type-C circuit breakers:
16A 200m @+10C°
CERTIFICATES : CSTB. EAC. déclaration UE (CE). IP66/68. RoHS. REACH. UV-résistant